We are using online corrosion electrode of type electrical resistance to monitore corrsoion rate in cooling system of cappacity 27000m3 , we use NALCO company treating program since 2 months ,( we were using KURITA program) we have 3 online probe of 2 electrodes , and 3 corrosion coupon In same place of probes, the problem we found that the reading of corrosion rate are increasing and when we checked the electrode we found some rust deposite at the end of electrode although the corrosion coupons condition is good !! We continue replace the electrode and reading is good in first two day and begin to rise again !we don’t know reason for that ,, we adjust flowrate to electrode 40 litre per hour ,, we don’t now is this rate is recommended or what ! Any help ?!