EPA CT was developed to assess the performance of disinfection systems mostly related to drinking water biological quality. EPA CT Tables provide CT values for the major drinking water disinfectants such as: chlorine (free chlorine), chloramines, ozone, and chlorine dioxide. The CT for chloramines was developed based on disinfection data collected from preformed chloramine (which means chloramine solution was prepared and the chloramines were already formed in the solution before being used for the disinfection). However, in the field, current chloramine application uses the sequential method where free chlorine is applied first for certain period and then ammonia is introduced in the system to produce the chloramines. This method of chloramine production is different from the method that EPA used (preformed method of chloramine production) to prepare the CT tables. MIOX (a mixed oxidant system) operates a mixed oxidant solution including free chlorine, hydrogen peroxide, and others that are simultaneously produced in the disinfection solution. MIOX uses EPA CT tables to assess its disinfection performance, although the disinfectants are simultaneously produced in their systems. Here multiple disinfectants are systematically formed in the process, while EPA CT tables are based on single disinfectant systems. From the above two cases, it can be observed that the method of disinfectant production seems to be irrelevant to the use of EPA CT tables.