I'm working with the OpenStudio Plugin to generate an IDF in order to use it as input in an EnergyPlus simulation.

I'm working with a 1-story building, with 5 rooms, a VRF System and 3 VRF Terminals.

After exporting the IDF, when I run the simulation I obtain these three warnings:

1. VRFCOOLCAPFT output is equal to 1.136 at rated conditions (instead of 1.0):

** Warning ** GetVRFInput: AirConditioner:VariableRefrigerantFlow="VRF SYSTEM" curve values

* ~~~ ** ... Cooling Capacity Ratio Modifier Function of Low Temperature Curve Name = VRF SYSTEM VRFCOOLCAPFT 1 output is not equal to 1.0 (+ or - 10%) at rated conditions.

** ~~~ ** ... Curve output at rated conditions = 1.136

2. COOLINGEIRLOWPLR minimum value of X = 0.500 is out of range. It must be