In ADS cooling system ,the suggest suitable method to find adsorption temperature and regeneration temperature for ammonia-activate carbon pair.Guide us.
Lower limit is governed by either absorption or solidification or crystallisation of fliuds being handling and higher temperature is governed by separation or withstanding capacity of fluids.
Adsorption temperature is usually close to the ambient temperature, while regeneration temperature is the one allows to process the most part of the adsorbate according to the heat source: e.g. if I'm using low temperature heat (solar energy at 90-100°C) I can efficiently regenerate a Silica-Gel or a SAPO34 or other kind of similar zeo-type materials; I can't, instead, regenerate a 4A or 13X zeolite type. I suggest to have a look to adsorption curves and trace the adsorption cycle on them in order to understand if you are efficiently using the adsorbent material.