Does anyone have Kundur 2 area network modelled on DigSilent? I am having trouble getting the Eigen values for transient state. I am able to get similar results for load flow calculations. I would really appreciate if someone can help me on this.
I am having the same problem the eigen value analysis does not match the result given in the kundur's book. if u get the values right kindly let me know as well
Hello @jawwad, I am student trying to rebuild the two area system in DIGSILENT. I am not getting the right Eigen values. Can you help me here? I can send my pfd file to look into if you want. Let me know asap.
Eigen values for two area system in DIgSILENT should be close to given in the book but you will not get the excat eigen vlaue in any software because each software use a different method to reach to eigen values. The following papers discuss this issue in detail:
Thank You for references., I just wanted to know the standard current values of the system i.e. in the transmission lines and weather there is a transformer considered in the loads if yes, what is the MVA and the voltage ratings of the transformers?
sorry but i dont understood your question properly i can give you my model. Hope this will solve your problem. The eigen values for inter area and intera area modes in this simualtion are close to one given n the book
if you can share your model here, it would be really helpful. Is it in power factory? My question was in power factory, I have to enter the current value in the definition of the transmission line, and I don't find a right value and my second question was about the transformer used at the load buses, I have seen two models used, one with transformers and the other without. I want to be sure which is right and what is the rating of the transformers used (voltage and MVA rating)