As in many Techniques like ROCOF or Vector Shift (VS) are works on the principle that at the moment of islanding formation there will be an power imbalance, if there is no power imbalance how we can detect the islanding?
You can also use dQ/dt> detection since the most DG work with power factor (cos phi=1) or close to 1 . If the generator is opened disconnect from network with full balance between the production and consumption Pg=PL you will still have consumption of reactive power for plant own motors , trafo etc. Then power factor decrease to 0,95 or less and you have deviation of Q-reactive power which can be detected. Such practical solution we use and it works on one biomass power plant..
ROCOF> Rate of Chane of Frequency and VVS Voltage vector shift> are classical protection for anti-islanding protection but can not help in case of the balance between generator production and consumption in the tie-line of PCC. The rate of change of angle can be efective (but you will not have the chane of angle in perfect balance) If the value P=0.00 kW or close to this value these protection function can not detect. If you have AR- Automatic Reclosing on overhead lines very offen with fast opening in a cycle of tie-line breaker (about 300-400 ms is pause time in Croatia) ROCOF and VVS can not detect it. Also other passive protection f>> or f can not be used, Only the chagne of the reactive power maye be detected since almost all RES work with cos phi close to 1 beacause of feeding tariff pay only for active power P, and if the tie-line breker is open generator need to suppy its own reactive consumption in power plant and that can be detected with high probability and fast tripping.