There are two parallel centrifugal pumps which pump about 25000 ton/h water toward a dry cooling tower. The system is using a sigma-pressure indicator system (to be sure that the coolers are completely filled up and prevent any extra pressure in flexible junctions). The outlet butterfly valves are designed for three positions, include 1. closed, 2. completely open and 3. half open (usually when one of them is out of service)

The cooling tower is designed for the ambient temperature of about 16 C. In the winter, due to the extra decrease in ambient temperature (usually between -5 C to 10 C), we have to close the air dampers before air coolers. However, the electrical consumption of the pumps is constants, because there is not a mass flow control system or an electric speed control driver.One good suggest is decreasing in mass flow rate of the pumps. but there is a problem with controlling the outlet valves position.

One good suggest is decreasing in mass flow rate of the pumps, while can open the dampers more than usual. in this case, the electrical consumption of the pumps decrease. But there is a problem with controlling the outlet valves position and how to define a new sigma-pressure index for best operation conditions.

I will appreciate if anyone can help me.

More Gholamreza Ahmadi's questions See All
Similar questions and discussions