Dear Collegues
Imworking on distributed generation dynamic behavior. Does anybody know about Gas and Disel Generator sets inertia? Im looking for DGs in range of 1 -5 MW.
You can use H=1.76 for 0.5-1 MW diesel generator.
https://www.nrcan.gc.ca/sites/www.nrcan.gc.ca/files/canmetenergy/files/pubs/2012-060-eng.pdf
For gas turbine, you can use H=2 - 3
http://www.sname.org/HigherLogic/System/DownloadDocumentFile.ashx?DocumentFileKey=d54396ec-9e36-49eb-a3d8-ae16f98c1694