where Vm is the peak phase(phase-neutral) supply voltage.
Vdc= (3(root 3)/pi)Vp*(root 2)= 2.33909Vp
where Vp is the rms phase voltage i.e, Vm=root 2*Vp
Vdc=2.33909* Vll/(root3)= 1.3505Vll
This Vll is taken as Vp if each phase of secondary of transformer is delta connected and For star connected secondary transformer winding Vp of each winding=Vll/(root3))